' Input file for DTU 10MW controller
' November 7, 2013
'
'
'
' Rated power [kW]                         
10000.0
'
' Minimum rotor speed [rad/s]
0.628  
' Rated rotor speed [rad/s]
1.005  
' Maximum allowable generator torque [Nm]
15.6e6  
' Minimum pitch angle, theta_min [deg], 
100.0    
' if |theta_min|>90, then a table of <wsp,theta_min> is read '
' from a file named 'wptable.n', where n=int(theta_min)
' Maximum pitch angle [deg]
90.0    
' Maximum pitch velocity operation [deg/s]
10.0    
' Frequency of generator speed filter [Hz]
0.2   
' Damping ratio of speed filter [-]
0.7    
' Frequency of free-free DT torsion mode [Hz], if zero no notch filter used
1.85   
' Partial load control parameters 
' Optimal Cp tracking K factor [kNm/(rad/s)^2], 
' Qg=K*Omega^2, K=eta*0.5*rho*A*Cp_opt*R^3/lambda_opt^3    
0.100131E+08
' Proportional gain of torque controller [Nm/(rad/s)]
0.683456E+08 
' Integral gain of torque controller [Nm/rad]
0.153367E+08 
' Differential gain of torque controller [Nm/(rad/s^2)]
0.0    
'
' Full load control parameters
' Generator control switch [1=constant power, 2=constant torque]
1
' Proportional gain of pitch controller [rad/(rad/s)]
0.524485
' Integral gain of pitch controller [rad/rad]
0.141233  
' Differential gain of pitch controller [rad/(rad/s^2)]
0.0    
' Proportional power error gain [rad/W]
0.4e-8 
' Integral power error gain [rad/(Ws)]
0.4e-8 
' Coefficient of linear term in aerodynamic gain scheduling, KK1 [deg]
198.32888   
' Coefficient of quadratic term in aerodynamic gain scheduling, KK2 [deg^2] &
' (if zero, KK1 = pitch angle at double gain)
693.22213   
' Relative speed for double nonlinear gain [-]
1.3    
'     Cut-in simulation parameters
' Cut-in time [s]
0.1    
' Time delay for soft start of torque [1/1P]
4.0    
'     Cut-out simulation parameters
' Cut-out time [s]
5000     
' Time constant for 1st order filter lag of torque cut-out [s]
5    
' Stop type [1=linear two pitch speed stop, 2=exponential pitch speed stop]
1
' Time delay for pitch stop 1 [s]
1    
' Maximum pitch velocity during stop 1 [deg/s]
1.5    
' Time delay for pitch stop 2 [s]
1    
' Maximum pitch velocity during stop 2 [deg/s]
1.5    
'     Expert parameters (keep default values unless otherwise given)
' Lower angle above lowest minimum pitch angle for switch [deg]
0.5    
' Upper angle above lowest minimum pitch angle for switch [deg], if equal then hard switch
0.5    
' Ratio between filtered speed and reference speed for fully open torque limits [%]
95.0    
' Time constant of 1st order filter on wind speed used for minimum pitch [1/1P]
5.0    
' Time constant of 1st order filter on pitch angle used for gain scheduling [1/1P]
5.0    
'     Drivetrain damper
' Proportional gain of active DT damper [Nm/(rad/s)], requires frequency in input 10
0.0  
'	  Over speed
' Over speed percentage before initiating shut-down
1500.0  
'     Additional non-linear pitch control term
' Err0 [rad/s] 
0.0  
' ErrDot0 [rad/s^2]
0.0  
' PitNonLin1 [rad/s]
0.0  
' Ng
50.0
' Min pitch table 
'
'nlines (1 lines)
' followed directly by (WS in m/s, pitch in deg)
' no comments in between 
22
4.00	2.581
5.00	1.8
6.00	0.789
7.00	0
8.00	0
9.00	0
10.00	0
11.00	0
12.00	4.507
13.00	7.088
14.00	8.991
15.00	10.598
16.00	12.042
17.00	13.376
18.00	14.63
19.00	15.824
20.00	16.968
21.00	18.071
22.00	19.141
23.00	20.181
24.00	21.192
25.00	22.175






















     
     
     
     
     
     
      
      
      
      
      
      
      
      
      
      
      
      
      
      
      